Setting the LIS-SV

This section supplements the “LIS-SV” product manual. The parameters described here are only available if the LIS-SV is used in an ABULiner control unit.

 

 

Overview of the 'ABULiner' parameter level

The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.

 

Parameter

Designation

See

5.10

Calling up the parameter level

Accessing the 'ABULiner' parameter level

5.11

Activating the LIS-SV for the ABULiner

Activating/deactivating the LIS-SV for the ABULiner

5.11

Setting the gear ratio

Setting the gear ratio

5.12

Activating double lifting speed

Activating double lifting speed on the LIS-SV

5.14

Setting the run-on time of the auxiliary fan

Setting the run-on time of the auxiliary fan

 

Danger during setting work!

During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things.  This means the wire rope hoist cannot be monitored for excess load, among other things.

This in turn means the load could fall and kill or injure people!

Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes!

 

 

Accessing the 'ABULiner' parameter level

All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.

 

 

 

    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

    Open the menu of the LIS-SV. See the documentation “Load indicator system LIS-SV”.

 

 

Enter button

Arrow buttons

    Select parameter 5.10.

    Press ENTER.

●   The 'ABULiner' parameter level is activated.

●   Parameter 5.11 is displayed.

 

 

Exiting the 'ABULiner' parameter level

Enter button

Arrow buttons

    Select parameter 5.99.

    Press ENTER.

●   The previous parameter level is reactivated.

●   Parameter 5.10 is displayed.

 

 

Activating/deactivating the LIS-SV for the ABULiner

The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.

In the ABULiner mode (a value is set for parameter 5.11):

─     The LIS-SV can monitor the total load for a maximum of two wire rope hoists.

─     Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.

─     A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV cannot be used.

─     Parameter 4.5 (setting for load-controlled switching point) is not available.

 

 

In the normal mode (no value is set for parameter 5.11):

─     Operation of the ABULiner Lifting/Lowering unit is not possible.

─     The LIS-SV can monitor the total load for up to three wire rope hoists.

─     Input F3 serves in measuring the load of a third wire rope hoist.

─     A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV can be used.

─     Parameter 4.5 (setting for load-controlled switching point) can be used.

 

 

Setting the gear ratio

The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.

 

 

Cable speed

 

    Read off the type designation at the type plate of the wire rope hoist.

    Read off the cable speed.

 

 

    From this table, select the gear ratio that matches the cable speed.

 

Cable speed

Hoist motor GM

32 m/min at 50 Hz
38 m/min at 60 Hz

25 m/min at 50 Hz
30 m/min at 60 Hz

20 m/min at 50 Hz
24 m/min at 60 Hz

16 m/min at 50 Hz
19 m/min at 60 Hz

800.4

50.01

63.49

77.77

98.16

800.5

47.03

60.04

74.66

95.03

1000.6

54.43

68.91

84.00

105.1

1000.7

54.60

68.06

81.45

104.6

2000.3

58.22

74.23

91.19

118.4

3000.4

73.61

93.92

118.4

152.9

5000.3

85.14

109.3

132.8

169.0

5000.4

80.20

104.9

127.7

160.6

6000.3

94.69

118.5

149.6

182.7

7000.1

118.0

148.3

182.6

232.0

Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.

 

 

Enter button

Arrow buttons

    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

    Select parameter 5.11.

    Press ENTER.

●   The set value is displayed.

If the value is 0.00, the function is deactivated.

●   Hold ENTER pressed.

●   CODE is displayed.

    Hold ENTER pressed.

 

 

Enter button

Arrow buttons

    Enter the code 1443.

    Press ENTER briefly.

 

 

Enter button

Arrow buttons

    Set the value from the table.

If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0.  In this case, set the value to zero first.

    Press ENTER briefly.

 

 

A Alma Indomavel Pdf Link Download Gratis Apr 2026

I should also consider that the user's primary language might be Portuguese, so suggesting Portuguese online stores or checking if the book is available on Google Books or Amazon in Portuguese. Additionally, maybe there are free summaries or analysis online if the user is looking for study materials. Clarify that while the full book can't be downloaded for free, summaries or related content might be available under fair use.

Wait, the user wrote "A Alma Indomável." Let me check if that's the correct title and if there's an official English version. Some Portuguese titles might not have English translations. If that's the case, the user might need a Portuguese library or bookstore. Also, maybe the user is in a country where access is an issue, so suggesting libraries or legal torrent sites if available. a alma indomavel pdf link download gratis

I should also consider that the user might not know about free public domain books or open-access resources. But "A Alma Indomável" doesn't ring a bell as a public domain work. Let me confirm the author's lifetime. If the author is still alive, it's definitely under copyright. If not, maybe the work is in the public domain in the country of origin. But the user is asking for a free PDF, so they might be looking for a study guide or summary. Could "A Alma Indomável" be a study guide itself? Maybe the user got confused between the original work and the study material. Alternatively, there might be a free version provided by the author or publisher for educational purposes. I should also consider that the user's primary

Finally, make sure the tone is helpful and not dismissive of the user's request. Acknowledge their interest and provide constructive options to access the book legally. Wait, the user wrote "A Alma Indomável

I should start by acknowledging the request and then clarify the importance of copyright. Maybe mention that the book is protected by intellectual property laws. Then, suggest legal alternatives like purchasing from online stores or checking the library. Also, offer to help find the title in Portuguese if there's any confusion.

Wait, the user might not be aware that the book is available for purchase. Including a disclaimer that I can't provide pirated links but can direct them to legitimate sources is essential. Also, perhaps mention that if the user is in a low-income area, they might qualify for free e-book programs or that libraries offer digital access through services like OverDrive. If the user is in a place with a good library system, that's a good alternative.

I need to structure the paper in a helpful way. Start by explaining why free download isn't possible and the legal implications. Then, offer alternative options. Maybe include steps on how to access the book legally. Also, check if there are any free excerpts or samples available online. Highlight the importance of supporting authors to maintain the literary ecosystem. Maybe provide links to the publisher's website or official platforms where the user can legally obtain the book.

 

 

Only for auxiliary fans

 

Setting the run-on time of the auxiliary fan

The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.

 

Enter button

Arrow buttons

    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

    Select parameter 5.14.

    Press ENTER.

●   The set value is displayed.

 

 

Enter button

 

    Set the value to between 3 and 10 minutes using the arrow buttons.

    Press ENTER.